a) LED Indicators

  • Voltage Indicator (V): On in voltage display mode; off otherwise.
  • Speed Indicator (RPM): On in speed display mode; off otherwise.
  • Current Indicator (A): On in current display mode; off otherwise.
  • Power Indicator (W): On in power display mode; off otherwise.
  • Tank Full Indicator (Tank): On when the tank is full; off otherwise.
  • Well Dry Indicator (Well): On when the well is out of water; off otherwise.
  • Solar Mode Indicator (MPPT): The closer it is to the maximum power point, the faster the MPPT light flashes; off when stopped.
  • Power & Run Indicator (Power): Flashes when the pump is stopped; stays on when running.

b) Buttons

  • Switch: Short press to cycle through speed, current, voltage, and power parameters.
  • Enter: Select/confirm in the settings interface.
  • Up: Increase level.
  • Down: Decrease level.
  • ON/OFF: Motor run switch. When turned off, the display shows “OFF” and other buttons are inactive. When a fault code is displayed, short press to quickly clear the fault.

c) Settings
The settings use a two-level menu:

  • Long press the settings button to enter the settings list.
  • Short press Enter to enter detailed settings.
  • Short press again to exit detailed settings.
  • Long press again to exit the settings list.
  • The system will also exit automatically after a period of inactivity.
  • The motor will stop when entering settings.

When P0.0 ≠ 12, other settings cannot be modified.
The default value of P0.0 is 0.
To modify settings, first set P0.0 to 12.
When P0.0 is set to 21, the system will restore factory settings.

The following is the detailed settings list:

Function CodeNameDefault ValueDescription
P0.0User Access Permission0~2112: Enable modification access
21: Restore factory settings
P0.1Dry-run Protection Enable10: Disabled    1: Enabled
P0.2Power Supply Mode00: Auto detection
1: Battery
2: Solar power
P0.3Voltage Protection Hysteresis15Range: 2~40
P0.4DC Undervoltage Protection ValueModel dependentAlarm will trigger when voltage is below this value
P0.5Dry-run Power Point 1Model dependentNo-load power at 2000 RPM
P0.6Dry-run Power Point 2Model dependentNo-load power at 3000 RPM
P0.7Dry-run Power Point 3Model dependentNo-load power at 4000 RPM
P0.8Dry-run Power Point 4Model dependentNo-load power at 5000 RPM
P0.9Maximum Speed Setting4000Range: 1000~4000
P9.8Pump ModelModel dependent
P9.9Program Version + Manufacturer CodeModel dependent